Power station or generator · Home backup power: wattage, capacity, runtime

Power station or generator

Your situation

Task

Appliances · 7 of 7

Selected appliancesqty × power × hours
Wi-Fi router
×W ×h96 Wh
6%
Optical network terminal (ONT)
×W ×h64 Wh
4%
Gas boiler (controls + pump)
×W ×h768 Wh
44%start ×1.5
Refrigerator
×W ×h280 Wh
16%start ×3.0
LED bulb
×W ×h150 Wh
9%
Laptop
×W ×h325 Wh
19%
Smartphone (charging)
×W ×h60 Wh
3%

Autonomy

Outage length8 h

You need a power station from 400 W / 2,600 Wh or a generator from 0.9 kW

7 appliances · outage 8 h · energy 1.7 kWh

Energy per outage

1,743Wh

with inverter losses 2,051

Running power

365W

20% of EcoFlow DELTA 3 Plus rated power

Starting peak

565W

start: Refrigerator

Required capacity

2,600Wh

DoD 95% · reserve 10%

How long it will last

Move the duration — the cards update at once

Outage length8 h
EcoFlow DELTA 3 Plus · Optimal9 h 41 min
EcoFlow DELTA 2 Max · With headroom12 h 46 min

T = C · DoD · (1 − reserve) / (P_avg / η + P_self) · the tick is the chosen duration, 8 h

What drains the battery

Energy per outage by appliance

1.7 kWh
  • Critical
  • Desirable
  • Can do without
Gas boiler (controls + pump)power-hungry768 Wh · 44%
Laptop325 Wh · 19%
Refrigerator280 Wh · 16%
LED bulb × 3150 Wh · 9%
Wi-Fi router96 Wh · 6%
Optical network terminal (ONT)64 Wh · 4%
Smartphone (charging) × 260 Wh · 3%
AppliancenP, Wt, hdutyE, Wh
Gas boiler (controls + pump)11208.000.80768
Laptop1655.001.00325
Refrigerator11008.000.35280
LED bulb3105.001.00150
Wi-Fi router1128.001.0096
Optical network terminal (ONT)188.001.0064
Smartphone (charging)2152.001.0060
Total1,743

E_i = n · P · t · duty · E_req = E_AC / η + E_DC / 0.95 + P_self · T

What you can leave out

Tick an appliance — the calculation updates at once

Peak load

Motors and compressors draw several times their rated power at start

Refrigerator: start ×3.0 = 300 W · system peak 365 + 200 = 565 W

ApplianceP, Wk startStart, WΔP, W
Refrigerator100×3.0300200
Gas boiler (controls + pump)120×1.518060

P_run = Σ P (simultaneous) + max P (in turn) · P_peak = P_run + max ΔP, ΔP = n · P · (k − 1)

Optimal+2 extra batteries

EcoFlow

DELTA 3 Plus

With your set9 h 41 min

left after 8 h: 17%

Capacity
3,072 Wh
Rated / peak
1,800 / 3,600 W
Inverter load
20%
UPS
10 ms
Weight
12.5 kg

90,550–154,295 ₴

Where to buy
With headroom+1 extra battery

EcoFlow

DELTA 2 Max

With your set12 h 46 min

left after 8 h: 37%

Capacity
4,096 Wh
Rated / peak
2,400 / 4,800 W
Inverter load
15%
UPS
20 ms
Weight
23.0 kg

113,870–171,192 ₴

Where to buy
GeneratorNot for a flat

Class

1 kW inverter

typical figures of the class

On a full tank24 h 6 min

Rated / max.
0.9 / 1.0 kW
Load
41%
Fuel
0.09 L/h · tank 2.1 L
An hour of running
5 ₴
Noise
≈ 52 dB

14,000–22,000 ₴

Warnings

1 item for your set

  • Note: A gas boiler needs a pure 50 Hz sine wave. If the boiler does not start from a station, the usual cause is phase dependence: the neutral must be earthed, or an isolating transformer is needed.

Note: an estimate for planning. Actual runtime depends on the appliance model, the temperature and battery wear.