Cable size and breaker · Size by current and ΔU, breaker rating and curve

Cable size and breaker

Load

household 0.95 · motors 0.8
Network
characteristic B: 3–5 × In · 5 × In in the calculation
Line purpose
Breaker characteristicby the load: B

Line

DBN: lighting 3 % · other 5 %
Conductor material
air 10–60 °C
bunched together, 1–20
from the intake to the board

VVGng-LS 3×2.5 mm² + B20 breaker

Ib 16.02 A ≤ In 20 A ≤ Iz 23 A · ΔU 2.98 %

Conductor size

2.5mm²

VVGng-LS 3×2.5

Breaker

B20A

3–5 × In

Design current

16.02A

Iz 23 A · 70 %

Voltage drop

2.98%

6.85 V · limit 5 %

Warnings

  • Protect a socket circuit with an RCD of rated residual current no more than 30 mA.

    DBN V.2.5-23:2025, cl. 7.24

Single-line diagram

Hover a block or a field — the element and its figures light up

Board230 V · 1phB203–5 × InIb 16In 20Iz 23Ib ≤ In ≤ Iz ✓VVGng-LS 3×2.5L 25 mIz 23 A · ΔU 2.98 %3×2.5 mm²Load3.50 kWcos φ 0.95Ib 16 AU 223.2 V1234
Ib = P / (U · cos φ) = 3,500 / (230 · 0.95) = 16.02 A
  1. 1Supply / board230 V · single-phase
  2. 2Breaker B20In 20 A · 3–5 × In
  3. 3Cable VVGng-LS 3×2.5L 25 m · in a conduit or trunking on a wall, in a chase in a conduit
  4. 4LoadP 3.50 kW · cos φ 0.95

Recommended 2.5 mm² — set by current: a smaller section cannot carry the breaker

ДСТУ HD 60364-5-52, table B.52.2, B.52.4 · two loaded conductors · in a conduit or trunking on a wall, in a chase in a conduit · click a row to choose it

SectionIz', ALargest breakerΔU at 25 mShort circuitStatus
16.5—4.96 %Lmax 61.3 mIn 20 > Iz'
23B202.98 %Lmax 102.2 m✓ fits
30B251.86 %Lmax 163.6 m✓ fits
38B321.24 %Lmax 245.3 m✓ fits
52B500.74 %Lmax 408.9 m✓ fits
69B630.47 %Lmax 654.2 m✓ fits
90B800.30 %Lmax 1,022.2 m✓ fits
111B1000.21 %Lmax 1,431.1 m✓ fits
133B1250.15 %Lmax 2,044.4 m✓ fits

ΔU 2.98 % at 25 m · the 5 % limit is reached at 42 m

Voltage drop by length for 2.5 mm² and the neighbouring sections

Lmax 102.2 m — beyond the chart

ΔU = 2 · Ib · L · ρ · cos φ / S · ρ Cu 0.0225 Ω·mm²/m

Note: a planning estimate, not a substitute for a design. The final size and protection of the line are set by the electrical design.