Cable size and breaker · Size by current and ΔU, breaker rating and curve
Cable size and breaker
Load
Line
VVGng-LS 3×2.5 mm² + B20 breaker
Ib 16.02 A ≤ In 20 A ≤ Iz 23 A · ΔU 2.98 %
Conductor size
2.5mm²
VVGng-LS 3×2.5
Breaker
B20A
3–5 × In
Design current
16.02A
Iz 23 A · 70 %
Voltage drop
2.98%
6.85 V · limit 5 %
Warnings
Protect a socket circuit with an RCD of rated residual current no more than 30 mA.
DBN V.2.5-23:2025, cl. 7.24
Single-line diagram
Hover a block or a field — the element and its figures light up
- 1Supply / board230 V · single-phase
- 2Breaker B20In 20 A · 3–5 × In
- 3Cable VVGng-LS 3×2.5L 25 m · in a conduit or trunking on a wall, in a chase in a conduit
- 4LoadP 3.50 kW · cos φ 0.95
Recommended 2.5 mm² — set by current: a smaller section cannot carry the breaker
ДСТУ HD 60364-5-52, table B.52.2, B.52.4 · two loaded conductors · in a conduit or trunking on a wall, in a chase in a conduit · click a row to choose it
| Section | Iz', A | Largest breaker | ΔU at 25 m | Short circuit | Status |
|---|---|---|---|---|---|
| 16.5 | — | 4.96 % | Lmax 61.3 m | In 20 > Iz' | |
| 23 | B20 | 2.98 % | Lmax 102.2 m | ✓ fits | |
| 30 | B25 | 1.86 % | Lmax 163.6 m | ✓ fits | |
| 38 | B32 | 1.24 % | Lmax 245.3 m | ✓ fits | |
| 52 | B50 | 0.74 % | Lmax 408.9 m | ✓ fits | |
| 69 | B63 | 0.47 % | Lmax 654.2 m | ✓ fits | |
| 90 | B80 | 0.30 % | Lmax 1,022.2 m | ✓ fits | |
| 111 | B100 | 0.21 % | Lmax 1,431.1 m | ✓ fits | |
| 133 | B125 | 0.15 % | Lmax 2,044.4 m | ✓ fits |
ΔU 2.98 % at 25 m · the 5 % limit is reached at 42 m
Voltage drop by length for 2.5 mm² and the neighbouring sections
Lmax 102.2 m — beyond the chart
ΔU = 2 · Ib · L · ρ · cos φ / S · ρ Cu 0.0225 Ω·mm²/m
Note: a planning estimate, not a substitute for a design. The final size and protection of the line are set by the electrical design.