Heat loss · Heating power the house needs

Temperature conditions

by building type

design

Building size

Floor area — m²Walls — m²Perimeter — m

Windows

    Windows in total — m²

    Thermal resistance R

    • Walls— m²
    • Windows— m²
    • Roof— m²
    • Floor— m²

    The result will appear here

    To get a verdict and numbers, fill in the house dimensions.

    Enter the house dimensions — or pick it from the house collections

    Worked example

    example

    This is how the calculator evaluates a house's heat loss: its dimensions, windows and the thermal resistances of the envelope. Below are the example's inputs and the numbers the server returned for them; your own calculation starts from your own dimensions.

    Inputs
    ParameterValue
    House dimensions (W × L × H)10.4 × 12.5 × 3.2 m
    Windows6 pcs 1.5 × 1.5 m; 4 pcs 1.2 × 1.4 m
    Indoor temperature20 °C
    Outdoor temperature-22 °C
    R of walls3.33 m²·K/W
    R of windows0.71 m²·K/W
    R of roof5 m²·K/W
    R of floor4 m²·K/W
    Key numbers
    ParameterValue
    Required power5.25 kW
    Specific loss q40.4 W/m²
    Boiler with margin7 kW
    Mean U0.307 W/(m²·K)
    Demand per year11840 kWh